MUSH-2M
Product description
The module is designed to coordinate a two-wire SPS with fire and fire protection PPCs working with a four-wire fire alarm loop.
- Monitors the value of the current in the circuit of the two-wire alarm loop and, depending on its value, changes the state of the output key for the transmission of notifications "Duty mode", "Alarm" on the PPC
- Ensures the formation of the "Alarm" signal by breaking the circuit of the signal loop of the four-wire fire alarm loop
- Provides an optical indication of this "Alarm" state with a red indicator when:
- open circuit or short circuit in the circuit of the two-wire loop;
- activation of one or more detectors.
- Provides optical indication of the next operating mode with a green indicator
- Provides limitation of the amount of current in the event of a short circuit in the circuit of a two-wire fire alarm loop
- Allows you to turn off the power supply of the two-wire loop using the "RESET" button
Specifications
Characteristic
Value
Current consumption in standby mode:
no more than 25 mA
Overall dimensions:
no more than 65×55×20 mm
Mass:
no more than 0.05 kg
Range of input voltages:
10.2 – 13.8 V
Range of output voltages in alternate mode:
9.7 – 13.6 V
Short-circuit current in the circuit of a two-wire loop:
no more than 20 mA
The resistance of the two-wire SHS, at which the module generates the message "Alternative mode":
1.0 ± 3 kΩ
The resistance of the two-wire loop perceived by the module as the "ALARM" mode:
from 0 to 0.75 and above 3.3 kΩ
Current consumption in "Alarm" mode:
no more than 31 mA
The number of fire detectors connected to a two-wire alarm loop:
no more than 32