MUSH-3M

Product description

It is intended for matching the two-wire fire loop (FL) with security and fire control systems operating with a four-wire FL, as well as with the control system with variable-signal power supply of the FL

  • Monitors the value of the current in the two-wire fire loop and, depending on its value, changes the state of the output key for the transmission of notifications ("Standby mode", "Fire", "Malfunction") to the PC
  • Forms the message "Fire" when one or more fire detectors are triggered in the circuit of the two-wire fire loop by a jump-like decrease in resistance (increase in current) in the circuit of the signal loop of the PPC
  • Forms a "Fault" notification in the event of a break or short circuit in the circuit of the two-wire loop and in the absence of 12V power on the module (the optical indicator is turned off) by breaking the circuit of the signal line of four-wire alarm loop
  • Provides limitation of the amount of current in the event of a short circuit in the circuit of a two-wire fire alarm loop
  • Allows you to turn off the power supply of the two-wire loop using the "RESET" button

Specifications

Characteristic

Value

Current consumption in standby mode:

no more than 25 mA

Overall dimensions:

no more than 65×55×20 mm

Mass:

no more than 0.05 kg

The presence of an indication of the duty mode:

Yes

Current consumption in FIRE mode:

no more than 40 mA

Range of input voltages:

10.2 – 13.8 V

Range of output voltages in alternate mode:

9.7 – 13.6 V

Short-circuit current in the circuit of a two-wire loop:

no more than 20 mA

The resistance of the two-wire SHS, at which the module generates the message "Alternative mode":

1.4 ± 2.5 kΩ

The resistance of the two-wire loop perceived by the module as the "ALARM" mode:

from 0 to 1 kΩ

The number of fire detectors connected to a two-wire alarm loop:

no more than 32

Useful materials

Name Country Comment Open Download
Manual       Ukrainian
Сertificate UA(Ukraine) Declaration of compliance with the requirements of Ukrainian standards
Scheme       Image of the connection diagram in a packed cdr file in CorelDRAW format
Packed    

Educational materials

Section 9.2. Input-output devices (RT-2, MUSH-1M, MUSH-2M and MUSH-3M).
In section 9.2 of the informational materials "Components of fire protection systems", input - output devices, such as RT-2, MUSH-1M, MUSH-2M and MUSH-3M, are considered. which are produced by the private enterprise "ARTON". The technical solutions used in these products and protected by patents for intellectual property objects, technical characteristics of the products and schemes for connecting them to the fire alarm loops are given.


Click to view
 komponenty_spz_r92.pdf