Fire detector thermal maximum, designed to control the ambient temperature in closed rooms of various buildings and structures. When the threshold value of the ambient temperature in the protected room is exceeded, the detector generates a “FIRE ALARM” signal for the control panel. The “FIRE” mode is indicated by a red optical indicator.

    • The detector is designed for continuous round-the-clock operation with a PPC on a two-wire signaling loop (direct current or alternating sign) with a nominal supply voltage of 12 or 24 V.
    • The detector provides an indication of the next operating mode.
    • The detector corresponds to class A2 according to DSTU EN 54-5.

Specifications

Characteristic

Value

Supply voltage range:

9 - 30 V

Current consumption in standby mode at a maximum supply voltage of 30V:

no more than 0.15 mA

The voltage current in the "Fire" mode is set by an external resistor in the range of values:

5 - 30 мА

The method of connecting to the FACP:

two-wire AL

Overall dimensions:

not more than 80 × 27 mm

Mass:

no more than 0.05 kg

The presence of an indication of the standby mode:

Yes

Static operating temperature range:

54-70 º С

Useful materials

Name Country Comment Open Download
Manual       ukrainian
Сertificate UA(Ukraine) Valid from January 14, 2022 to January 13, 2025
Archive       Archive zip file of the old certificate
Packed    

Devices with which it is used

Auxiliary devices > Loop matching modules > MUSH-1M
Auxiliary devices > Loop matching modules > MUSH-2M
Auxiliary devices > Loop matching modules > MUSH-3M
Auxiliary devices > Loop matching modules > MUSH-6M
Auxiliary devices > Auxiliary devices > KR-6
Auxiliary devices > Auxiliary devices > KR-4T
Auxiliary devices > Auxiliary devices > UK-2
Auxiliary devices > Auxiliary devices > RT-2