0

newspaper-1-filled

RT-2

Product description

The T-shaped splitter RT-2 is designed to generate a “fault” signal in a 2-wire fire alarm loop with a T-shaped branch.

  • Can be used with reception and control devices "ARTON-02P", "ARTON-04P", "ARTON-08P", "ARTON-16P", "ARTON-32P" at voltage (13-15) V in the loop.
  • RT-2 due to T-shaped branching allows to reduce the volume of wire installation while maintaining control of the integrity of the fire alarm loop along its entire length, including in T-shaped branches.
  • RT-2 provides indication of interruptions in T-shaped branches with indicators of yellow color and at the same time forms a "fault" signal by short-circuiting the fire alarm loop, which is sent to the control panel.

Specifications

Characteristic

Value

Supply voltage:

13 - 15 V

The method of connecting to the PPK:

2-wire alarm loop

Overall dimensions:

no more than 61x53x18 mm

Mass:

no more than 0.05 kg

The resistance of the two-wire loop (without taking into account the resistance of the remote elements):

no more than 100 ohms

short-circuit current in the alarm loop circuit:

no more than 30 mA

Useful materials

Name Country Comment Open Download
Manual       russian
Сertificate UA(Ukraine) Declaration of compliance with Ukrainian standards
Scheme       Connection diagrams
Packed    

Educational materials

Section 9.2. Input-output devices (RT-2, MUSH-1M, MUSH-2M and MUSH-3M).
In section 9.2 of the informational materials "Components of fire protection systems", input - output devices, such as RT-2, MUSH-1M, MUSH-2M and MUSH-3M, are considered. which are produced by the private enterprise "ARTON". The technical solutions used in these products and protected by patents for intellectual property objects, technical characteristics of the products and schemes for connecting them to the fire alarm loops are given.


Click to view
 komponenty_spz_r92.pdf