FTL-BR
Product description
The maximum differential thermal fire detector with an indication of the duty mode, intended for monitoring the ambient temperature in closed rooms of various buildings and structures, including unheated ones.
Classification of detectors of the FT series
| Group | Name | Class | Response temperature | Indication of the standby mode |
| 1 | FT-A1 | A1 | 54 - 65 | - |
| FT -A2 | A2 | 54 - 70 | ||
| FT-B | B | 69 - 85 | ||
| FTL-A1 | A1 | 54 - 65 | ||
| 2 | FTL -A2 | А2 | 54 - 70 | + |
| FTL -B | B | 69 - 85 | ||
| FT - A1S | А1S | 54 - 65 | ||
| 3 | FT - A2S | A2S | 54 - 70 | - |
| FT - BS | BS | 69 - 85 | ||
| FTL - A1S | A1S | 54 - 65 | ||
| 4 | FTL - A2S | A2S | 54 - 70 | + |
| FTL - BS | BS | 69 - 85 | ||
| Maximum-differential thermal detectors with microcontroller signal processing and with an indication of the standby mode | ||||
| 5 | FTL - A1R | A1R | 54 - 65 | + |
| FTL - A2R | A2R | 54 - 70 | ||
| FTL -BR | BR | 69 - 85 | ||
- Type - maximum-differential
- Reacts to the rate of temperature rise
- Improved schematic solutions
- High resistance to false alarm
- Non-removable renewable
- Two-mode with remote return to the initial state
- Optical indication of the "Fire" mode with two LEDs
- Ease of installation and maintenance
- Compatibility with various FACP
- Wide range of supply voltage
Specifications
Characteristic
Value
Current consumption in standby mode:
0.1 mA
The method of connecting to the FACP:
two-wire AL
Габаритні розміри:
not more than 85 × 33 mm
Mass:
no more than 0.05 kg
The presence of an indication of the standby mode:
Yes
The method of forming the output signal:
contactless
Static operating temperature range:
69-85 º С
Class according to DSTU EN54-5
BR