FACP “SPEKTRA-6”
Product description
The fire alarm device is used to ensure a modern fire safety system at small and medium-sized facilities (shops, offices, banks, warehouses, etc.), by round-the-clock monitoring of the status of up to 6 alarm loops.
The device meets all requirements and standards of DSTU EN 54-2, DSTU EN 54-4 and DSTU EN54-21 (Type 1).
- Main features:
- 6 alarm loops;
- 2- or 4-wire connection of alarm loops;
- 2 outputs for notification;
- "Fire" and "Fault" outputs;
- Built-in GSM/GPRS communicator;
- Programming from the built-in keyboard or computer;
- An extended range of operating temperatures from minus 10 °С to 55 °С, which allows you to operate the device in extreme conditions of unheated rooms or metal trade containers;
- Built-in charging and control device for battery 12 V / 7 Ah.
Specifications
Characteristic
Value
Power supply from an alternating current network with a voltage of 230V (with a tolerance of minus 15% and 10%) with a frequency of (50±1) Hz;
The maximum power consumption of the device from the network:
15 W
Maximum current consumption from battery:
1,2 V
The average current consumption from the battery in standby mode:
0,14 A
Maximum long-term total current for external loads:
1 A
Period of determination of internal resistance (Ri max – 1 Ohm) battery:
30 min
The supply voltage of the AL on the Z1...Z6 contacts relative to the GND contacts when there is no load:
from 13,5 V to 14,5 V
The total resistance of the lines (wires) of the AL without taking into account the resistance of the terminating resistor:
no more than 220 ohms
Leakage resistance between the lines of the AL (with the terminating resistor disconnected), as well as between each line of the AL and the grounded body of the device:
not less than 50 kΩ
The minimum current increase in the AL circuit, which is evaluated by the device as a "FIRE" state:
5 mA
The minimum current reduction in the AL circuit, which is evaluated by the device as the "FIRE" state:
3 mA
The AL current, which is considered by the device as an interruption:
less than 3,3 мА
The DC current, which is considered by the device as a short-circuit:
more than 60 mA
The device allows you to connect up to 32 detectors of the type SPD-3, SPD-3.5, SPD-3.10, SPD-2B, SPD-3B, SPD-3.2, SPD-3.3, etc. to each bus;
The device allows the connection of active fire detectors manufactured by "ARTON" PE without installing current-limiting resistors to the AL;
The duration of the automatic reset (disconnect time) of the system during manual reset or verification of the AL:
(5 ±1) sec
The duration of the verification of the activation of the detector in the emergency room in the "Attention" state, upon detection of which the device switches to the "FIRE" mode:
2 min
The maximum load current of each of the outputs "S1", "S2", "DET", "+12V" (the total load current of all output switches must not exceed 1 A):
300 mA
The maximum load current of each of the outputs "FLT", "PG1", "PG2":
100 mA
The minimum values of the load current of the AL in standby mode:
not less than 3,5 мА
The time of technical readiness of the device after turning on the power source is no more than:
10 sec
Transmission of a malfunction signal to the ANRC(alarm notification receiving center):
up to 90 sec
The average service life of the device:
not less than 10 years
Useful materials
| Name | Country | Comment | Open | Download |
|---|---|---|---|---|
| Manual | Ukrainian | |||
| Сertificate | UA(Ukraine) | Valid from January 14, 2022 to January 13, 2025 | ||
| Instruction | purpose, technical characteristics, procedure for installation, programming and operation of the device | |||
| Article | FACP: regulatory requirements, traditional construction, innovative solutions (www.security-ua.com (2012)) |
Educational materials