ARTON-04P

Product description

Intended for the organization of centralized and autonomous fire protection of various objects through round-the-clock monitoring of the condition of up to 4 alarm loops (AL).

The device meets the requirements of the standards DSTU EN-54-2: 2003/Amendment No. 1 and DSTU EN 54-4:2003 / Amendment No. 2, DSTU-H CEN / TS 54-14:2009.

    • Each of the AL can be configured by the consumer as a fire AL without verification, with verification, or with the activation of 2 detectors, and dependencies of types A, B, C can also be set (according to the requirements of DSTU EN-54-2: 2003/ change No. 1);
    • The devices determine and display the following statuses of the security system: "On-duty mode", "Attention" (operation of the first detector in the security system), "Fire", "Fault - short circuit", "Fault - open circuit", "Security system disconnected", "malfunction of one of intelligent detectors in the AL":
    • The possibility of connecting passive and active detectors into one AL, building combined control panels using 2-wire and 4-wire connection schemes;
    • Determination of the following types of malfunctions and states: short circuit of the output keys, interruption of the loads of each of the output keys, lack of voltages supplying the output keys and AL, lack of 220V power supply voltage, absence, critical discharge or malfunction of the battery, etc.;
    • Availability of outputs: "Fire", "Fault", "Notification" ("Snd1" and "Snd2"), 2 programmable current outputs "AUX1" and "AUX2" and 2 programmable relays "Relay1" and "Relay2" ;
    • The possibility of connecting up to 4 independent detectors with chain integrity control (in accordance with the requirements of DSTU-H CEN / TS 54-14:2009);
    • The presence of an input for connecting an external backup power source with control of its serviceability;
    • There is no need for a current-limiting resistor when connecting detectors of the SPD-3, SPD-3.10, TPT, FT type to the two-wire AL;
    • The presence of a separate muting (disabling) alarm button;
    • Auto-memory function of the current of the standby mode of the AL;
    • The possibility of changing the detection thresholds of detectors from 1 to 16 mA;
    • The possibility of configuring devices using a PC.

Specifications

Characteristic

Value

Overall dimensions:

no more than 230х280х90 mm

Mass:

no more than 3,5 kg

The device is powered by an alternating current network with a voltage of 220 (+22-33) V and a frequency of (50 ± 1) Hz and/or from a sealed maintenance-free lead-acid battery with a nominal voltage of 12 V and a nominal capacity of 7 or 7.2 A/h and the final voltage of long-term discharge is 10.5 V. (AB is not included in the delivery set)

The maximum power consumption of the device from the network:

30W

Power consumption from the network in standby mode:

no more than 15 Вт

Maximum current consumption from the battery:

0,8 A

The maximum current consumption from the battery in standby mode:

0,2 A

The maximum current consumption from the battery, when the alternating current network is disconnected and the voltage on the battery is less than (10.5-1) V:

30 mA

The voltage at the contacts of the open output keys with a total load of the output keys up to 0.6 A - from 8.8 to 14 V. At the same time, the doubled amplitude of the pulsations does not exceed 0.5 V

The maximum voltage on the switched-off "Light/Sound" output switches, (resistors, "Fire" and "Fault" with a load resistance of 3.3 kΩ are included in the delivery set):

no more than 2,5 V

The maximum number of AL connected to the device:

4

Supply voltage at contacts AL1 - AL4 when there is no load:

15 (± 1 ) V

The voltage on the contacts AL1 - AL4 with a current in each of the AL up to 20 mA:

no less than 12 V

The total resistance of the lines (wires) of the AL without taking into account the resistance of the final resistor:

no more than 220 ohms

Leakage resistance between the lines of AL (when the terminating resistor is disconnected), as well as between each line of SHS and the device case:

not less than 50 kΩ

The minimum change in the current in the AL circuit (relative to the fixed AL base current), which is evaluated by the device as "FIRE":

plus 4 mA or minus 1,2 mA

The AL current, which is considered by the device as an interruption:

from 0 to 3 mA

The AL current, which is considered by the device as a short-circuit:

more than 24 mA

The device has short-circuit protection in the circuits of AL and output keys with malfunction indication

The device reacts to a change in the state of the AL when the duration of this change is at least 100 ms and does not issue a message about the change when the duration is less than 50 ms.;

The device allows you to connect up to 32 active detectors (type SPD-3, SPD-3.5, SPD-3.10, SPT-2B, SPT-ZB, etc.) to each fire alarm system, while the maximum current consumption by all fire detectors in the regular mode of operation should not exceed 3 mA;

The duration of the automatic reset (disconnect time) of the AL during the verification of the AL;

no less than 5 sec

Duration of waiting for reactivation in the "Attention" mode after resetting the AL, upon detection of which the device switches to the "FIRE" mode:

( 60 ± 6 ) sec

The maximum load current on the output "Light / Sound" ("L / S"):

500 mA

The maximum load current on each of the power outputs P1 and P2 of four-wire fire detectors:

200 mA

Maximum load current on the outputs: "Fire", "Fault", "Alarm", "Normal", "K1" - "K4":

40 mA

The minimum values of the current load of the device in alternate mode for each of the outputs: "Light/Sound", "Fire", "Fault", as well as in the circuits AL1 - AL4 - 3.5 mA (set using 3.3 kΩ resistors from the kit spare parts and accessories, see item 12)

The time of technical readiness of the device after turning on the power source is no more than:

20sec

Range of ratings of end resistors:

from 1 kΩ to 3.9 kΩ

The range of ratings of additional current-limiting resistors of active detectors:

from 0 to 1.2 kΩ.

Stabilized power supply AL:

(УКР) 15 (± 0,5 )

AL short-circuit current:

no less than 60 mA

The maximum current of outputs "Snd1", "Snd2":

500 mA

Maximum current of outputs "AUX1", "AUX2":

300 mA

Average working time before device failure:

no less than 40,000 hours

Useful materials

Name Country Comment Open Download
Manual       russian
Сertificate UA(Ukraine) (УКР) Термiн дiї 14 сiчня 2022 до 13 сiчня 2025
Сertificate MD(Moldova) The validity period is unlimited.
Scheme       Connection diagram of detectors FTL-A1R, FTL-A2R, FTL-ABR to FACP "Arton-02P, (-04P), (- 08P)".
Instruction       Brief instructions for putting into operation FACP "Arton-08P" ("Arton-02P", "Arton-04P") (in russian).
Archive       Manual, photo
Packed    

Devices with which it is used

FIRE ALARM CONTROL PANELS > PPKP "Arton" > ARTON-04P
FIRE ALARM CONTROL PANELS > PPKP "Arton" > ARTON-04P
FIRE ALARM CONTROL PANELS > PPKP "Arton" > ARTON-04P

Educational materials

Section 8.2. Fire receiving and control devices (requirements for FACP of the Arton-0XP series, block diagrams of technical solutions and patent numbers of Ukraine).
In section 8.2 of information materials "Fire protection system components", the requirements for FACP Arton-0XP series, which are produced by the private enterprise "ARTON", are considered. Block diagrams of technical solutions and patent numbers of Ukraine for intellectual property objects, thanks to which the required level of product quality was achieved, are given.


Click to view
 komponenty_spz_r82.pdf

Section 8.3. Arton-02P, Arton-04P, Arton-08P receiving and control fire equipment (construction features, recommendations for preparation for work).
In section 8.3 of informational materials "Components of fire protection systems", the consideration of FACP of the Arton-0XP series, which is produced by the private enterprise "ARTON", is continued. Features of construction are shown, recommendations for preparation for work are given, and examples of the operation of these devices are given.


Click to view
 komponenty_spz_r83.pdf

Section 8.4. Arton-02P, Arton-04P, Arton-08P reception and control devices for fire fighting (additional capabilities of the devices, which are achieved when configuring the products).
In section 8.4 of informational materials "Components of fire protection systems", the consideration of FACP of the Arton-0XP series, which is produced by the private enterprise "ARTON", is continued. Additional capabilities of devices, which are achieved when configuring products, are considered. Examples of changes in the configuration of devices are given.


Click to view
 komponenty_spz_r84.pdf

Section 8.5. Arton-02P, Arton-04P, Arton-08P fire receiving and control devices (BR4-4 relay unit, BSKT-1 telephone communicator, KM-GSM-3 communicator MCSY 425693.011-03, BSPK-1 PC communication unit).
In section 8.5 of the information materials "Components of fire protection systems" devices and blocks that complement the functionality of FACP series Arton-0XP, manufactured by the private enterprise "ARTON": BR4-4 relay block; telephone communicator BSKT-1; communicator KM-GSM-3 MCI 425693.011-03; block of communication with a personal computer BSPK-1.


Click to view
 komponenty_spz_r85.pdf