Product description

Base B2 is intended for connection of detectors SPD-3.10 to four-wire AL. Base B2 generates an output signal using relay contacts. When building a fire alarm loop on B2 bases, it is necessary to install a B6 or B8 base (B8 base with remote indicator) at the end of each AL. In such a system, the lack of supply voltage due to a break or removal of any electronic unit from the base leads to the formation of a “Fault” notification from this AL on the FACP.

Implementation of various functions using databases:

BaseNumber of contactsPresence of ZPOSThe presence of a relay Relay contactsConnection
B014---2-wire
B16+--2-wire
B27-1NO4-wire
B37-1NO4-wire
B48+1NO4-wire
B58+1NO4-wire
B6*8-2NC,NO4-wire
B7*8-2NC,NO4-wire
B8*9+2NC,NO4-wire
B9*9+2NC,NO4-wire
* final base

Specifications

Characteristic

Value

Напруга живлення:

12 ± 1,8 V

The method of connecting to the FACP:

four-wire AL

Resistance between contacts "1" and "2" when the electronic unit is removed:

no more than 200 kΩ

Resistance between contacts "1" and "2" with installed electronic unit:

no more than 2 ohms

The method of forming the output signal:

distance between relay contacts

Useful materials

Name Country Comment Open Download
Manual       Ukrainian
Scheme       Compressed CorelDRAW CDR file
Packed    
Presentaion       Packed presentation files (in Ukrainian and Russian)
Packed    

Devices with which it is used

Fire detectors > Smoke optical > SPD-3.10
Auxiliary devices > Detector bases > Base B6
Auxiliary devices > Detector bases > Base B8