Base B5

Product description

The B5 base is intended for connecting the SPD-3.10 detector with NO output contacts of the relay to the 4-wire AL and remote indicator. Base B5 generates an output signal using relay contacts. When building a fire alarm loop on B5 bases, it is necessary to install a B7 or B9 base at the end of each fire AL (B9 base with remote indicator). In such a control unit, the lack of supply voltage due to a break or removal of any electronic unit from the base leads to the formation of a “Fault” notification on the control panel in this control unit.

Implementation of various functions using databases:

BaseNumber of contactsPresence of ZPOSThe presence of a relay Relay contactsConnection
B014---2-wire
B16+--2-wire
B27-1NO4-wire
B37-1NO4-wire
B48+1NO4-wire
B58+1NO4-wire
B6*8-2NC,NO4-wire
B7*8-2NC,NO4-wire
B8*9+2NC,NO4-wire
B9*9+2NC,NO4-wire
* final base

Specifications

Characteristic

Value

The method of connecting to the PPK:

four-wire AL

Resistance between contacts "1" and "2" when the electronic unit is removed:

no more than 200 kΩ

Resistance between contacts "1" and "2" with installed electronic unit:

no more than 2 ohms

The method of forming the output signal:

by closing the relay contacts

Useful materials

Name Country Comment Open Download
Manual       Ukrainian
Presentaion       ppt presentation file

Devices with which it is used

Fire detectors > Smoke optical > SPD-3.10
Auxiliary devices > Detector bases > Base B7
Auxiliary devices > Detector bases > Base B9