Base B6

Product description

The B6 base is intended for use as the final base in a four-wire AL together with the B2 or B4 bases (with NC contacts). Base B6 forms an output signal using the contacts of the main relay and additionally monitors the performance of the four-wire AL. In such a system, the lack of supply voltage due to a break or removal of any electronic unit from the base leads to the formation of a “Fault” notification from this AL on the FACP.

Implementation of various functions using databases:

BaseNumber of contactsPresence of ZPOSThe presence of a relay Relay contactsConnection
B014---2-wire
B16+--2-wire
B27-1NO4-wire
B37-1NO4-wire
B48+1NO4-wire
B58+1NO4-wire
B6*8-2NC,NO4-wire
B7*8-2NC,NO4-wire
B8*9+2NC,NO4-wire
B9*9+2NC,NO4-wire
* final base

Specifications

Characteristic

Value

The method of connecting to the FACP:

four-wire AL

Resistance between contacts "1" and "2" when the electronic unit is removed:

no more than 200 kΩ

Resistance between contacts "1" and "2" with installed electronic unit:

no more than 2 ohms

The method of forming the output signal:

by opening the relay contacts