0

newspaper-1-filled

Vektor-1

Product description

The reception and control device with the function of controlling automatic means of fire protection of the “Vector-1” series is intended for the organization of centralized and autonomous protection of various objects from fires, is part of the fire alarm system, control of fire extinguishing, smoke removal, ventilation and other automatic devices . The device combines the functions of a fire receiving and control device and a control device, meets the requirements of DSTU EN54-2, DSTU EN54-4, DSTU EN54-21, DSTU 4469-1.

The device configuration option and its coding can be selected using symbol generator, and its symbols can be deciphered with the help of the corresponding decoder.

  • A wide selection of design options depending on the purpose and complexity of the object:
    • internal power supply voltage (24 V or 12 V. By default - 24 V);
    • the number of input-output channels (from 8 to 32);
    • the number of fire protection keys (up to 16);
    • each object (exit, output) of the system has end-to-end numbering (addressing);
    • built-in control panel for two fire extinguishing zones;
    • a compartment for installation on a DIN rail for up to 20 relays;;
    • communication units and interface collectors.
  • The multifunctionality of the fire protection system:
    • autonomous operation of each key;
    • cascade work up to eight keys;
    • operation of keys in duplicating schemes.
  • Free binding of outputs (keys) by logical formulas to states (events) in the control system and keys, including without the use of additional devices and software:
  • Low electricity consumption due to:
    • the use of fire extinguishers with an edge capacitor;
    • dynamic power supply of logical SHS (discrete inputs);
    • power supply of SHS and keys with unstable voltage (there are no voltage converters that reduce the efficiency of the device);
  • Convenient controls and indications:
    • simple menu (no more complicated than a simple mobile phone);
    • standard telephone keyboard;
    • easy-to-read information on the display (large illuminated symbols);
    • versatility, multifunctionality, increased reliability and maintainability;
  • Up to 20 devices can be combined into a system with a single control and management.
  • A PC can be used for convenient monitoring.
  • Seven operating modes of each input-output channel:
    • fireman with repeated inspection with an edge capacitor;
    • fireman with re-checking with edge resistor;
    • firefighter without repeated inspection with edge capacitor;
    • firefighter without rechecking with an edge resistor;
    • logical (discrete input);
    • protective;
    • exit ( key ).
  • Each fire protection key can be programmed for the following functions:
    • entrance with automatic detectors;
    • entrance with manual detectors;
    • input for connecting the "Automatics off" switch;
    • input for connecting switches and "Locking" sensors;
    • input for connecting the "Reset Delay" button;
    • input for connecting "Emergency stop" switches;
    • input for connecting switches "Emergency extinguishing start";
    • delay time programming;
    • programming of the OTV supply time.
  • The device works with ani tips:
    • automatic and manual detectors;
    • manual start sensors, start blocking sensors.

Specifications

Characteristic

Value

Voltage in the DC and at the outputs for 24 V power supply:

from 20 V to 30 V

Voltage in the SS and at the outputs for 12 V power supply:

from 9.5 V to 15 V

Current in the alarm loop:

no more than 30 mA

The switching current of the key of each input-output channel:

up to 50 mA

Switching current of keys with full load control for connecting detectors:

up to 200 mA

Switching current of keys intended for controlling fire extinguishing means:

up to 4 A

The sound signal is restored when a new event occurs:

Fire detectors power off time when resetting the fire alarm system:

4 - 6 sec

The delay time for the processing of the fire alarm system after turning on the power (including during reset) of fire detectors:

4 - 6 sec

Time until automatic reset of the primary fire alarm state (Attention):

5-6 min

Useful materials

Name Country Comment Open Download
Manual       ukrainian
Сertificate UA(Ukraine) Valid from January 14, 2022 to January 13, 2025
Сertificate MD(Moldova) The validity period is unlimited
Soft       Drivers, configurator
Packed    
Presentaion       ukrainian
Instruction       ukrainian
Archive       Passports
Packed    

Educational materials

Section 11.1. Fire receiving and control devices of the Vector-1 series (construction possibilities, recommendations for marking).
Control panel of the "Vector-1" series with the function of controlling automatic means of fire protection, manufactured by the private enterprise "ARTON". features of construction of the devices of this series are shown, recommendations regarding the designation of the device for ordering it are provided.


Click to view
 komponenty_spz_r111.pdf

Section 11.2. Fire receiving and control devices of the Vector-1 series (technical solutions, block diagrams).
Section 11.2 of the informational materials "Fire protection system components" discusses technical solutions that are used in the Vector-1 series control panel with the function of controlling automatic fire protection devices produced by the private enterprise "ARTON". Shown are block diagrams of devices of this series, which were protected by patents for inventions and utility models.


Click to view
 komponenty_spz_r11.2.pdf

Section 11.3. Fire receiving and control devices of the Vector-1 series (BCP, BC, BIIU).
In section 11.3 of informational materials "Components of fire protection systems", the constructive solutions that are applied in individual blocks of FACP of the "Vector-1" series with the function of controlling automatic means of fire protection, manufactured by the private enterprise "ARTON", are considered. The following units are considered in this section: unit of the central processor CPU; block of keys BC; display and control unit BIiU.


Click to view
 komponenty_spz_r113.pdf