IC-485 interface collector
Product description
IC RS485 – RS485 interface collector is a component FACP “Vektor-1” and is designed to create a hierarchical group of devices in accordance with Clause 4.3.2 of DSTU
- Installation requirements:
- The interface collector (IC) must be installed in each device of the "Vector-1" system;
- RS 485 communication lines consist of two channels (duplication), which must be performed with a twisted pair (shielded or unshielded);
- ± 5% 0.25 W resistors must be installed on the terminals of the last RS 485 IC communication lines in the chain (to which one communication line is connected);
- At the terminals of RS 485 CI communication lines of intermediate devices, the communication lines must be connected directly at the terminal ("T" - similar connections must be excluded).
Useful materials
| Name | Country | Comment | Open | Download |
|---|---|---|---|---|
| Manual | ukrainian | |||
| Сertificate | UA(Ukraine) | Valid from January 14, 2022 to January 13, 2025 |