ARTON-16P – discontinued
Product description
Intended for the organization of centralized and autonomous protection of various objects from fires, by round-the-clock monitoring of the state of up to 16 fire alarm loops, fixing signals about the occurrence of a fire or malfunction, issuing alarm notifications (about a fire, accident, malfunction of an unauthorized autopsy) on the notification device (light and sound) and on the central monitoring panel. The device generates control signals for up to 22 output lines (including switching on control devices for fire extinguishing, smoke removal, facility ventilation systems).
PPK “ARTON-16P” meets all standards of DSTU EN54 – 2: 2003 and DBN V 2.5-13-98.
- The device determines and displays with optical indicators and on the alphanumeric display:
- general states: modes "Fire", "Fault", "Disconnect", "Test";
- notification of malfunctions: disconnection or malfunction of outputs (fire, malfunction, alert, communication channels with the CMP), system error, key activation delay;
- states of the alarm loops ("Standby mode", "Attention", "Fire", "Short-circuit", "Open circuit", "AL disabled", "AL testing");
- states of output switches ("Short circuit in load", "Load break", "On delay", "Activation", "Disconnect", "Testing");
- state of the power supply unit and battery ("Absence of battery", "Charge of battery", "Critical discharge of battery", "Battery normal", "Availability of 220V" or "Absence of 220V", "Charger malfunction");
- The device provides:
- protection against unauthorized access to the inside of the case (opening or breaking the cover):
- automatic recharging of the battery and protection against its incorrect connection;
- protection of all output keys against short-circuits with automatic restoration of the initial state after elimination of the short-circuit;
- integrity control of the load chain of all output keys.
- The device implements multi-level access to control functions and the possibility of programming using the built-in keyboard of the following parameters and functions:
- Viewing and setting parameters of AL;
- fixation of the base currents of the AL (current of the AL in the alternate mode):
- setting of symbolic names of AL;
- viewing and setting parameters of output keys;
- setting the symbolic names of the output keys;
- changing user and engineer passwords;
- setting user rights to control the AL;
- setting user rights to manage exits;
- event log management;
Specifications
Characteristic
Value
Overall dimensions:
not more than 410 x 610 x 120 mm
Mass:
no more than 10 kg
The device is guaranteed to change its state when the duration of exposure is more than 100ms and does not change its state when the duration of exposure is less than 50ms.
The device allows you to connect up to 32 active detectors (such as SPD-3, SPD-3.5, SPD-3.10, SPT-2B, SPT-3, etc.) to each fire AL, while the maximum current consumption by all active fire detectors located in this fire AL, should not exceed 3 mA.
The output activation delay time is set by the user from the interval , seconds:
0 ... 255 in steps of 1
The time of the active state of the outputs is set by the user from the interval , seconds:
1 ... 65535 in steps of 1
The time of the active period in the passive output state is set by the user from the interval, seconds:
0 ... 25,5 in steps of 0,1
The time of the passive period in the passive output state is set by the user from the interval , seconds:
0 ... 25,5 in steps of 0,1
The time of the active period in the active output state is set by the user from the interval , seconds:
0 ... 25,5 in steps of 0,1
The time of the passive period in the active output state is set by the user from the interval, seconds:
0 ... 25,5 in steps of 0,1
The duration of transient processes when switching the output from the active to the passive state is set by the user from the interval, seconds:
0 ... 255 in steps of 1
Each output has the possibility of setting the inverse mode of operation.
The maximum load current for each of the outputs, mA:
no more than 30
Number of users:
9 (8 operators and 1 engineer)
User password length, characters:
0 ... 16
Time of technical readiness of the device after turning on the power source, seconds:
no more tjan 30
Average operating time for device failure, h:
no less than 4000
The device is powered by an alternating current network with a voltage of 220 (+22-33) V and a frequency of (50 ± 1) Hz.
The device is powered by sealed, maintenance-free lead-acid batteries with a nominal voltage of 12V, a full charge voltage of 14.4V, a nominal capacity of 16 to 18 Ah, and a final long-term discharge voltage of 10.5V. (AB is not included in the delivery set).
The maximum power consumption of the device from the alternating current network, W:
no more than 40
Power consumption from the alternating current network in standby mode, W:
no more than 12
Maximum current consumption from AB, A:
no more than 2,5
The maximum current consumption from the AB in standby mode, A:
no more than 0,55
The maximum current consumption from the battery, when the alternating current network is disconnected and the voltage on the battery is less than (10.5 - 1) V, mA:
no more than 200
Total load of output keys, A:
no more than 0,8
Voltage at the contacts of the open output keys (at the maximum total load of the output keys), In:
8,8 ... 15
Doubled amplitude of pulsations on open output keys, In:
no more than 0,5
Supply voltage at the contacts of the SHS when there is no load in the 12V AL mode, V:
15 ± 0,5
Supply voltage at the contacts of the AL when there is no load in the 24V SHS mode, V:
24 ± 0,5
The total resistance of the signal lines (wires) of the AL without taking into account the resistance of the terminating resistor, Ohm:
no more than 470
Leakage resistance between the lines of SHS, as well as between each line of AL and the device body, kΩ:
no less than 5
Modes of operation of the security system according to the type of detectors to be connected (depending on the type of ID):
(УКР) активний ШС, пасивний ШС, комбінований ШС
Modes of operation of the fire service according to the type of decision-making about the state of "Fire":
transition to the "Fire" state upon activation of 1 or more PIs with or without verification
The value of the increment (increase) of the current of the first active detector, relative to the basic current of the SMAL, is programmed by the user and is selected from the range, mA:
(УКР) 0,5 ... 8 з кроком 0,5
The value of the reduction of the current of the first active detector, in relation to the base current of the SMAL, is programmed by the user and is selected from the range, mA:
0,5 ... 8 in steps of 0,5
AL current, which is considered by the device as an interruption, mA:
less than 3
Current AL, which is considered by the device as short circuit, mA:
more than 2
The device has protection against short circuit in the circuits of AL and output keys with malfunction indication.
The time of automatic reset of the system in the "Verification" state is set by the user in the interval, seconds:
1 ... 20 in steps of 1
The waiting time for readiness after reset in the "Verification" state is set by the user in the interval, seconds:
1 ... 20 in steps of 1
The waiting time for reactivation after reset in the verification mode is set by the user in the interval , seconds:
1 ... 255 in steps of 1