Base B3

Product description

The B3 base is designed for connecting the SPD-3.10 detector with NO output contacts of the relay to a four-wire AL.

Base B3 generates an output signal using relay contacts. When building a fire alarm loop on B3 bases, it is necessary to install a B7 or B9 base (B9 base with remote indicator) at the end of each AL. In such a AL, the lack of supply voltage due to a break or removal of any electronic unit from the base leads to the formation of a “Fault” notification from this AL on the FACP.

Implementation of various functions using databases:

BaseNumber of contactsPresence of ZPOSThe presence of a relay Relay contactsConnection
B014---2-wire
B16+--2-wire
B27-1NO4-wire
B37-1NO4-wire
B48+1NO4-wire
B58+1NO4-wire
B6*8-2NC,NO4-wire
B7*8-2NC,NO4-wire
B8*9+2NC,NO4-wire
B9*9+2NC,NO4-wire
* final base

Specifications

Characteristic

Value

Supply voltage:

12 ± 1,8 V

The method of connecting to the FACP:

two-wire AL

Resistance between contacts "1" and "2", with the electronic unit removed:

no more than 200 kΩ

Resistance between contacts "1" and "2", when the electronic unit is installed:

no more than 2 ohms

Useful materials

Name Country Comment Open Download
Manual       Ukrainian
Presentaion       ppt presentation file

Devices with which it is used

Fire detectors > Smoke optical > SPD-3.10
Auxiliary devices > Detector bases > Base B7
Auxiliary devices > Detector bases > Base B9